Detail publikace

A Process Integration Method for Total Site Cooling, Heating and Power Optimisation with Trigeneration Systems

Jamaluddin, K. Wan Alwi, S.R. Manan, Z.A. Hamzah, K. Klemeš, J.J.

Anglický název

A Process Integration Method for Total Site Cooling, Heating and Power Optimisation with Trigeneration Systems

Typ

článek v časopise ve Web of Science, Jimp

Jazyk

en

Originální abstrakt

Research and development on integrated energy systems such as cogeneration and trigeneration to improve the efficiency of thermal energy as well as fuel utilisation have been a key focus of attention by researchers. Total Site Utility Integration is an established methodology for the synergy and integration of utility recovery among multiple processes. However, Total Site Cooling, Heating and Power (TSCHP) integration methods involving trigeneration systems for industrial plants have been much less emphasised. This paper proposes a novel methodology for developing an insight-based numerical Pinch Analysis technique to simultaneously target the minimum cooling, heating and power requirements for a total site energy system. It enables the design of an integrated centralised trigeneration system involving several industrial sites generating the same utilities. The new method is called the Trigeneration System Cascade Analysis (TriGenSCA). The procedure for TriGenSCA involves data extraction, constructions of a Problem Table Algorithm (PTA), Multiple Utility Problem Table Algorithm (MU PTA), Total Site Problem Table Algorithm (TS PTA) and estimation of energy sources by a trigeneration system followed by construction of TriGenSCA, Trigeneration Storage Cascade Table (TriGenSCT) and construction of a Total Site Utility Distribution (TSUD) Table. The TriGenSCA tool is vital for users to determine the optimal size of utilities for generating power, heating and cooling in a trigeneration power plant. Based on the case study, the base fuel source for power, heating and cooling is nuclear energy with a demand load of 72 GWh/d supplied by 10.8 t of Uranium-235. Comparison between conventional PWR producing power, heating and cooling seperately, and trigeneration PWR system with and without integration have been made. The results prove that PWR as a trigeneration system is the most cost-effective, enabling 28% and 17% energy savings as compared to conventional PWR producing power, heating and cooling separately.

Anglický abstrakt

Research and development on integrated energy systems such as cogeneration and trigeneration to improve the efficiency of thermal energy as well as fuel utilisation have been a key focus of attention by researchers. Total Site Utility Integration is an established methodology for the synergy and integration of utility recovery among multiple processes. However, Total Site Cooling, Heating and Power (TSCHP) integration methods involving trigeneration systems for industrial plants have been much less emphasised. This paper proposes a novel methodology for developing an insight-based numerical Pinch Analysis technique to simultaneously target the minimum cooling, heating and power requirements for a total site energy system. It enables the design of an integrated centralised trigeneration system involving several industrial sites generating the same utilities. The new method is called the Trigeneration System Cascade Analysis (TriGenSCA). The procedure for TriGenSCA involves data extraction, constructions of a Problem Table Algorithm (PTA), Multiple Utility Problem Table Algorithm (MU PTA), Total Site Problem Table Algorithm (TS PTA) and estimation of energy sources by a trigeneration system followed by construction of TriGenSCA, Trigeneration Storage Cascade Table (TriGenSCT) and construction of a Total Site Utility Distribution (TSUD) Table. The TriGenSCA tool is vital for users to determine the optimal size of utilities for generating power, heating and cooling in a trigeneration power plant. Based on the case study, the base fuel source for power, heating and cooling is nuclear energy with a demand load of 72 GWh/d supplied by 10.8 t of Uranium-235. Comparison between conventional PWR producing power, heating and cooling seperately, and trigeneration PWR system with and without integration have been made. The results prove that PWR as a trigeneration system is the most cost-effective, enabling 28% and 17% energy savings as compared to conventional PWR producing power, heating and cooling separately.

Klíčová slova anglicky

Co-generation; Pinch analysis; Process integration; Storage system; Total site heat integration; Trigeneration system; Trigeneration system cascade analysis; Cooling; Cooling systems; Cost effectiveness; Digital storage; Energy conservation; Heating; Industrial plants; Power generationTrigeneration plant; Cascade analysis; Co-generation; Heat integration; Pressurized water reactors

Vydáno

16.03.2019

Nakladatel

MDPI AG

Místo

MDPI, ST ALBAN-ANLAGE 66, CH-4052 BASEL, SWITZERLAND

ISSN

1996-1073

Ročník

6

Číslo

12

Strany od–do

1030–1040

Počet stran

10

BIBTEX


@article{BUT160785,
  author="Jiří {Klemeš},
  title="A Process Integration Method for Total Site Cooling, Heating and Power Optimisation with Trigeneration Systems",
  year="2019",
  volume="6",
  number="12",
  month="March",
  pages="1030--1040",
  publisher="MDPI AG",
  address="MDPI, ST ALBAN-ANLAGE 66, CH-4052 BASEL, SWITZERLAND ",
  issn="1996-1073"
}